Improve Your Boiler’s Combustion Efficiency PDF Print E-mail
Written by USDOE Office of Industrial Technologies   
Thursday, 01 July 2010 08:01

Improve Your Boiler’s Combustion Efficiency

Combustion Efficiency
Operating your boiler with an optimum amount of excess air will minimize heat loss up the stack and improve combustion efficiency. Combustion efficiency is a measure of how effectively the heat content of a fuel is transferred into usable heat. The stack temperature and flue gas oxygen (or carbon dioxide) concentrations are primary indicators of combustion efficiency.

Given complete mixing, a precise or stoichiometric amount of air is required to completely react with a given quantity of fuel. In practice, combustion conditions are never ideal, and additional or “excess” air must be supplied to completely burn the fuel.

The correct amount of excess air is determined from analyzing flue gas oxygen or carbon dioxide concentrations. Inadequate excess air results in unburned combustibles (fuel, soot, smoke, and carbon monoxide) while too much results in heat lost due to the increased flue gas flow—thus lowering the overall boiler fuel-to-steam efficiency. The table relates stack readings to boiler performance.

Combustion Efficiency for Natural Gas
Excess, % Combustion Efficiency
Flue Gas Temperature Minus Combustion Air Temperature, °F
Air Oxygen 200 300 400 500 600
9.5 2.0 85.4 83.1 80.8 78.4 76.0
15.0 3.0 85.2 82.8 80.4 77.9 75.4
28.1 5.0 84.7 82.1 79.5 76.7 74.0
44.9 7.0 84.1 81.2 78.2 75.2 72.1
81.6 10.0 82.8 79.3 75.6 71.9 68.2

Assumes complete combustion with no water vapor in the combustion air.

On well-designed natural gas-fired systems, an excess air level of 10% is attainable. An often-stated rule of thumb is that boiler efficiency can be increased by 1% for each 15% reduction in excess air or 40°F reduction in stack gas temperature.

Example
A boiler operates for 8,000 hours per year and consumes 500,000 million Btu (MMBtu) of natural gas while producing 45,000 lb/hour of 150-psig steam. Stack gas measurements indicate an excess air level of 44.9% with a flue gas minus combustion air temperature of 400°F. From the table, the boiler combustion efficiency is 78.2% (E1). Tuning the boiler reduces the excess air to 9.5% with a flue gas minus combustion air temperature of 300°F. The boiler combustion efficiency increases to 83.1% (E2). Assuming a fuel cost of $8.00/MMBtu, the annual savings are:

Annual Savings = Fuel Consumption x (1–E1/E2) x Fuel Cost
= 29,482 MMBtu/yr x $8.00/MMBtu
= $235,856

Flue Gas Analyzers
The percentage of oxygen in the flue gas can be measured by inexpensive gas- absorbing test kits. More expensive (ranging in cost from $500 to $1,000) hand- held, computer-based analyzers display percent oxygen, stack gas temperature, and boiler efficiency. They are a recommended investment for any boiler system with annual fuel costs exceeding $50,000.

Oxygen Trim Systems
When fuel composition is highly variable (such as refinery gas, hog fuel, or multi- fuel boilers), or where steam flows are highly variable, an online oxygen analyzer should be considered. The oxygen “trim” system provides feedback to the burner controls to automatically minimize excess combustion air and optimize the air-to- fuel ratio.

Adapted from an Energy TIPS fact sheet that was originally published by the Industrial Energy Extension Service of Georgia Tech.

FOR ADDITIONAL INFORMATION, PLEASE CONTACT:
EERE Information Center
1-877-EERE-INF (1-877-337-3463)

Industrial Technologies Program
Energy Efficiency and Renewable Energy
U.S. Department of Energy
Washington, DC 20585-0121
 

Add comment

Security code
Refresh

Saving Energy on Conveyor Belts
09/06/2010 | Western Area Power Administration

(original article available here) Technical help Case example July 2003 Question: What can be done to save energy on conveyor belt systems? One of our utility's customers operates outdoor conveyo [ ... ]


Energy Roadmap Projects Put NWFPA Membership on the Road
02/06/2010 | Pam Barrow

Energy Roadmap Projects Put NWFPA Membership on the Road In January 2009, NWFPA adopted an aggressive goal to reduce member-wide energy (electricity and fossil fuels) intensity (energy use per unit o [ ... ]


Other Articles